From https://www.justanswer.com/ythi • JustAnswer Customer: how do you do a power reset on a tempstar furnace? • HVAC Guru: HVAC TECH: Hello, Go to the breaker panel and shut off the circuit breaker to the unit for 1 full minute and turn the power back on. • JustAnswer Customer: I had the breaker off for an hour and the inducer motor still came back on when the breaker was turned back on. • HVAC Guru: HVAC TECH: The pressure switch must be stuck closed. • HVAC Guru: HVAC TECH: That is why the motor comes on right away. • HVAC Guru: HVAC TECH: You need to check the pressure switch. • HVAC Guru: HVAC TECH: It sounds like it is just bad and stuck closed causing the issue. • HVAC Guru: HVAC TECH: That code will come right back if that switch is stuck closed. • JustAnswer Customer: Is there any way to unstick it? • JustAnswer Customer: It worked fine until I started trying to get the a/c compressor to come on. • HVAC Guru: HVAC TECH: You need to get at the switch. • HVAC Guru: HVAC TECH: Try to remove the the pressure switch and suck through the port on the switch see if it clicks. • HVAC Guru: HVAC TECH: If not it is likely stuck closed. • HVAC Guru: HVAC TECH: Normally if they stick they are just bad and need to be replaced, but check the tube to it for any blockages that could cause the issue as well. • JustAnswer Customer: is the gas valve relay contact behind the coil mounted on the valve? • Pearl Wilson: Assistant: If you have a home improvement or appliance question and want to chat with an expert now visit justanswer.com/ythi
#############################