CALCULATION OF SUBTRANSIENT TRANSIENT STEADY STATE REACTANCE – PART – 05











>> YOUR LINK HERE: ___ http://youtube.com/watch?v=Daa3GKbm03s

For detailed notes please visit http://zenmurali.blogspot.in/ • CALCULATION OF SUB-TRANSIENT, TRANSIENT, STEADY STATE REACTANCE – PART – 05 • PROBLEM • A synchronous generator is connected to an infinite bus through a 138 kV transmission line, as shown in the figure. A three phase fault occurs on the line near the CB1. Before the short circuit, the receiving-end voltage was 1.0 per unit, unity power factor and the generator was 80 percent loaded, on the basis of its MVA rating. Determine the sub-transient, transient, and synchronous short-circuit currents.

#############################









Content Report
Youtor.org / YTube video Downloader © 2025

created by www.youtor.org