Temperature controller Masibus 5040 settings for modulation purpose multi action
>> YOUR LINK HERE: ___ http://youtube.com/watch?v=Z-_4iFRZFZA
Controller is being used as a PID for auto. operation of 3 way-valve through modulation function of PID. It helps in functioning of control output i.e. 4-20mA as per input temperature sensor e.g. rtd sensor, k-type etc. • Settings for working as a modulation with 3way valve: • Level-1 = AtUn no, Pb 50, t1 120, td 30, dFCt 0.01, Ct 10, dC 20, db 1.0, Pb.SH 0, • t1.L 100, Ar 0, rAAP none • Level 2 = A1SP 45, A1tp PuAH, A1HY 0.2, A1LC norA, A1dY 10..... • Level 3 = inPt rtd, PuH1 850, PuLo -199.9, dP 0, ot Cur, CoH1 100, CoLo 0, PuSC none, SPAd LoCL, odir rEu, SPno 1, FLtr 5, Po 0, dr1 no, dr2 no, dr3 no, dr4 no, • Level 4= Srno ⁷, bAUd 9600, PrSt PnS2, rtrt 4-20, rtru Pu, rdir dir, rtrH 105, rtrl -5.0, AtHY 5.0, tout 60, POd 0, • • Join us for becoming a social development and awareness volunteer: • https://prayaasekpahal.wordpress.com/... • For health awareness information, please visit : https://healthjaagran.com/ • For health awareness videos, please visit you tube channel: Tikendra - Health Jaagran: Health Wellness
#############################